Switched Shunt Model: SVSMO1
Some important SVC Control Considerations when running Transient Stability.
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tb1 < 0.5*Mult*TimeStep then Tb1 = 0, ElseIf 0.5*Mult*TimeStep < Tb1 < Mult*TimeStep then Tb1 = Mult*TimeStep
- If 0.0 < Tb2 < 0.5*Mult*TimeStep then Tb2 = 0, ElseIf 0.5*Mult*TimeStep < Tb2 < Mult*TimeStep then Tb2 = Mult*TimeStep
- If 0.0 < Tdelay1 < 0.5*Mult*TimeStep then Tdelay1 = 0, ElseIf 0.5*Mult*TimeStep < Tdelay1 < Mult*TimeStep then Tdelay1 = Mult*TimeStep
- If 0.0 < Tdelay2 < 0.5*Mult*TimeStep then Tdelay2 = 0, ElseIf 0.5*Mult*TimeStep < Tdelay2 < Mult*TimeStep then Tdelay2 = Mult*TimeStep
- Xc1: Xc1 value should matchthe Xc value in the power flow model, if not the same the then Xc1 parameter is autocorrected to the Xc value of the power flow model.
- Kiv: If Kiv > 1/(2*TimeStep) then Kiv = 1/(2*TimeStep)
- Kis: If Kis > 1/(2*TimeStep) then Kis = 1/(2*TimeStep)
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If SlowB > Vrmax, then Vrmax = SlowB or if SlowB < Vrmin, then Vrmin = SlowB
- If Vref > Vefrmax, then Vrefmax = Vref or if Vref < Vrefmin, then Vrefmin = Vref
- If Verr > Vemax, then Vemax = Verr or if Verr < Vemin, then Vemin = Verr
- If Bpi > Bmax, then Bmax = Bpi or if Bpi < Bmin, then Bmin = Bpi
Model Equations and/or Block Diagrams
Parameters:
| UVSBmax | Maximum capacitive limit during undervoltage strategy |
| UV1 | Under Voltage Setpoint 1, pu |
| UV2 | Under Voltage Setpoint 2, pu |
| UVT | Under Voltage Trip Setting Time, sec |
| OV1 | Over Voltage Setpoint 1, pu |
| OV2 | Over Voltage Setpoint 2, pu |
| UVtm1 | Under Voltage Trip Time 1, sec |
| UVtm2 | Under Voltage Trip Time 2, sec |
| OVtm1 | Over Voltage Trip Time 1, sec |
| OVtm2 | Over Voltage Trip Time 2, sec |
| Flag1 | MSS Switching enabled(1) or disabled(0) |
| Flag2 | Liner(0) or Non-linear(1) Slope |
| Xc1 | Slope (nominal linear slope or first section of piecewise linear slope, pu/pu) |
| Xc2 | Slope of second section of piecewise linear slope, pu/pu |
| Xc3 | Slope of third section of piecewise linear slope, pu/pu |
| Vup | Upper Voltage Break-point for non-linear slope, pu |
| Vlow | Lower Voltage Break-point for non-linear slope, pu |
| Tc1 | Voltage measurement lead time constant, sec |
| Tb1 | Voltage measurement lag time constant, sec |
| Tc2 | Lead time constant for transient gain reduction, sec |
| Tb2 | Lag time constant for transient gain reduction, sec |
| Kpv | Voltage regulator proportional gain, pu/pu |
| Kiv | Voltage regulator integral gain, pu/pu |
| Vemax | Max. allowed voltage error, pu |
| Vemin | Min. allowed voltage error, pu |
| T2 | Firing delay time constant, sec |
| Bshrt | Short-term max. capacitive rating of the SVC, pu |
| Bmax | Continuous max. capacitive rating of the SVC, pu |
| Bmin | Continuous min. inductive rating of the SVC, pu |
| Tshrt | Short-term rating definite time delay, sec |
| Kps | Proportional gain of slow-susceptance regulator, pu/pu |
| Kis | Integral gain of slow-susceptance regulator, pu/pu |
| Vrmax | Max. Allowed PI controller output of slow-susceptance regulator, pu |
| Vrmin | Min. Allowed PI controller output of slow-susceptance regulator, pu |
| Vdbd1 | Steady-state deadband, pu |
| Vdbd2 | Inner voltage deadband, pu |
| Tdbd | Definite time deadband delay, sec |
| PLLdelay | PLL delay in recovering if voltage remains below UV1 for more than UVtm1, sec |
| Eps | Small delta added to the susceptance bandwidth, MVAr |
| Blcs | Large threshold for switching MSS in capacitive side, MVAr |
| Bscs | Small threshold for switching MSS in capacitive side, MVAr |
| Blis | Large threshold for switching MSS in inductive side, MVAr |
| Bsis | Small threshold for switching MSS in inductive side, MVAr |
| Tmssbrk | MSS breaker switch delay, sec |
| Tdelay1 | Definite time delay for large switching threshold, sec |
| Tdelay2 | Definite time delay for small switching threshold, sec |
| Tout | Discharge time for mechanically switched capacitors, sec |